During 2017 by the State enterprise "VPKiTS", intended for installation of the burners, working on wood fuel pellets (pellets). We get the BY 300149357.006 – 2017.
During 2017 installation of boilers produced by our own production KVDG-0,095 (95kW power), working for pellets, in the boiler room "Bath №4».
Pellet boilers own production of different capacities are installed on a modular automated transportable boiler, in the boiler room "Olgovo-school". Besides, the company regularly takes part in competitions held in the Republic on the production of pellet boilers. Manufactured boilers for GP Liozno,Polotsk,Orsha.
Boiler heating hot water is designed for operation complete with a "pellet" burner. Powered by solid fuel (pellets), a working water pressure up 0,3 MPa and the maximum water temperature at the boiler outlet to + 95 ° C, It designed for heating individual houses and buildings of household purpose, equipped with water heating systems with forced circulation of hot water and.
The main parameters are summarized in Table
The main parameters are summarized in Table
parameter name | parameter value | |||
KB-ed-0,026-95 | KB-ed-0,045-95 | KB-ed-0,075-95 | KB-ed-0,095-95 | |
1.type of boiler | Steel fire tube hot water | |||
2. Estimated fuel - pellets, their heat of combustion, MJ / kg: | 16,5-19,0 | |||
3. Teploproyzvodytelnost, kW | 26 | 45 | 75 | 95 |
4. Specific fuel consumption kg / kW, no more | 0,25 | |||
5. Boiler efficiency, %, no less | 86 | 88 | ||
6. Flue gas temperature at the boiler outlet, WITH, no more. | 150 | 160 | ||
7. Operating pressure of water, MPa | 0,1 -0,4 | 0,1 - 0,6 | ||
8. The minimum water temperature at the boiler inlet,oC, no less, (tvh) | 45 | 55 | 55 | 55 |
9. The estimated water temperature at the boiler inlet,oC | 70 | 70 | 70 | 70 |
10. The maximum water temperature at the boiler outlet,oC, no more (outgoing gas) | 95 | 95 | 95 | 95 |
11. Vacuum the boiler, on, no more | 40 | |||
12. The volume of water in the boiler, m3, no less | 0,1 | 0,2 | 0,3 | 0,4 |
13. hydraulic resistance, MPa, no more, | 0,02 | 0,02 | 0,02 | 0,02 |
14. Nominal water flow, m3/no | 1,1 | 1,8 | 3,0 | 3,8 |
15. Minimum water flow rate, m3/no | 0,5 | 0,8 | 1,4 | 1,8 |
16. aerodynamic resistance, on, no more | 20 | 20 | 25 | 30 |
17. Weight, kg, no more | 350 | 700 | 900 | 1100 |
18. dimensions, mm no more:
Length Width Height |
1000
1000 1600 |
1600
1000 1400 |
1900
1000 1400 |
2200
1000 1400 |